VOC Gas Monitor and Controller

Faraday manufactures VOC Monitors and VOC Controllers indoor Air quality application.
Download PDF
Features
- The Faraday VOC Monitor gas sensor module provides state of the art gas measurement in a flexible cost effective package.
- Each module is ready to use with multi-point calibration
- Outputs include analog voltage, relay and status indicators with optional RS232, RS485 and LED (blue) or LCD display.
Applicaions
- Perchlorethylene monitoring for dry cleaning machines
- Food and beverage
- Sanitation & Refrigeration
- chemical process emissions detection
- building monitoring systems
- Waste Water - Plant protection, process monitoring and odour
- detection
- Aviation - Monitoring fuel spillages at air bases and airports
- Manufacturing industry - Monitoring discharges and processes which include VOCs
TECHNICAL SPECIFICATIONS
| . |
|
Sensor Type
|
Analytic GSS Technology
Gas sensitive Semiconductor
|
|
Sensor
|
VOC 0-500 ppm |
| 0-5V out scale |
0 - 500 |
| LDL |
1 ppm |
Accuracy
|
± 10 ppm 0 - 200 ppm ± 10%
200 - 500 ppm
|
| Resolution |
1 ppm |
Response Time (T90)
|
< 60 s |
Sampling Method
|
Fan |
Operating Temp
|
-0°C to 40°C
|
| Relative Humidity |
5 to 95% (non-condensing) |
| Operational mode |
Continous control or Alarm |
| Warm up time |
10 minutes (max. Accuracy) |
| Display |
3.5 digit LED |
| Relay set point |
User configurable |
| Digital output |
RS232 |
| Analog output |
0 - 5 VDC (8 bit) |
|
Relay output
(no internal alarm)
|
24 V; 5A(max.) |
Alarm option (no relay output) |
Internal piezo 85 db @ 30cm |
| Power supply |
12 VDC; 800 mA; Plug- in AC power adaptor supplied
|
| Enclosure rating |
IP20 & NEMA 1 equivalent |
| L x W x H |
200 x 120 x 85 (mm) |
| Weight |
700 gms |
| Approvals |
Part 15 of FCCRules
EN 61000 -6-3: 2001 EN 61000 -6-1: 2001
|
|
|
|
|
|
|
|
|
|